Abstract:
For evaluation of the structures against missile impact loads, including buildings located at nuclear power plants, it is usually desirable to idealize the structure with a single degree of freedom (SDOF) system. It is therefore convenient to introduce certain transformation factors to convert the mass and existing loads of the structure to equivalent mass, and load for the equivalent SDOF system.
This paper discusses the method for selecting the most applicable deflected shape function for a given impact location and investigates the transformation factors for non-central impacts on beams and slabs.